Sheathed and Non-Sheathed cables rated, 300/500V and 450/750V are insulated and/or sheathed cables for a variety of application from fixed wiring for power supply to sockets, switches, and lighting fittings of domestic and commercial buildings to flexible installation.
In fixed wiring applications, the cables are installed in conduit in walls or on surfaces. Non-sheathed cables are utilized in the internal wiring of distribution boards and switchboards.
The flexible cables are for connections to moveable equipment. Sheathed cables are either single or multicore cables. Our sheathed and non-sheathed products are BASEC approved, CE marked and manufactured in accordance with BS EN 50525-2-31, EN 50525-2-11, IEC 60227-3, IEC 60227-4, IEC 60227-5, BS 6004, and other customer specification.
Product Data Tables
GS IEC 60227-3, BS 6004
Rated Volage: | 450/750V |
Conductor: | Plain annealed copper conductor class 1&2, GS IEC 60228 |
Insulation: | PVC |
Maximum conductor operating temperature in normal use: | 70°C |
Nominal cross sectional area of conductor |
Class of conductor IEC 60228 |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 70°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
|||||
mm2 |
mm |
mm |
mm |
mm |
MΩ/km |
Ω/km |
1.5 |
1 |
0.7 |
2.6 |
3.2 |
0.011 |
12.10 |
1.5 |
2 |
0.7 |
2.7 |
3.3 |
0.010 |
12.10 |
2.5 |
1 |
0.8 |
3.2 |
3.9 |
0.010 |
7.41 |
2.5 |
2 |
0.8 |
3.3 |
4 |
0.009 |
7.41 |
4 |
1 |
0.8 |
3.6 |
4.4 |
0.0085 |
4.61 |
4 |
2 |
0.8 |
3.8 |
4.6 |
0.0077 |
4.61 |
6 |
1 |
0.8 |
4.1 |
5 |
0.007 |
3.08 |
6 |
2 |
0.8 |
4.3 |
5.2 |
0.0065 |
3.08 |
10 |
1 |
1.0 |
5.3 |
6.4 |
0.007 |
1.83 |
10 |
2 |
1.0 |
5.6 |
6.7 |
0.0065 |
1.83 |
16 |
2 |
1.0 |
6.4 |
7.8 |
0.005 |
1.15 |
25 |
2 |
12 |
8.1 |
9.7 |
0.005 |
0.727 |
35 |
2 |
1.2 |
9.0 |
10.9 |
0.0043 |
0.524 |
50 |
2 |
1.4 |
10.6 |
12.8 |
0.0043 |
0.387 |
70 |
2 |
14 |
12.1 |
14.6 |
0.0035 |
0.268 |
95 |
2 |
1.6 |
14.1 |
17.1 |
0.0035 |
0.193 |
120 |
2 |
1.6 |
15.6 |
|18.8 |
0.0032 |
0.153 |
150 |
2 |
1.8 |
17.3 |
20.9 |
0.0032 |
0.124 |
185 |
2 |
2.0 |
19.3 |
23.3 |
0.0032 |
0.101 |
240 |
2 |
2.2 |
22.0 |
26.6 |
0.0032 |
0.0775 |
300 |
2 |
2.4 |
24.5 |
29.6 |
0.003 |
0.0620 |
400 |
2 |
2.6 |
27.5 |
33.2 |
0.0028 |
0.0465 |
GS IEC 60227-3, BS 6004
Rated Voltage: | 450/750V |
Conductor: | annealed plain copper conductor class 5, GS IEC 60228 |
Insulation: | PVC |
Maximum conductor operating Temperature in normal use: | 70°C |
Nominal cross sectional area of conductor |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 70°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
1.5 |
0.7 |
2.8 |
3.4 |
0.010 |
13.3 |
2.5 |
0.8 |
4.1 |
4.1 |
0.009 |
7.98 |
4 |
0.8 |
4.8 |
4.8 |
0.007 |
4.95 |
6 |
0.8 |
5.3 |
5.3 |
0.006 |
3 3 |
10 |
1.0 |
6.8 |
6.8 |
0.0056 |
1.91 |
16 |
1.0 |
8.1 |
8.1 |
0.0046 |
1.21 |
25 |
1.2 |
10.2 |
10.2 |
0.0044 |
0.78 |
35 |
1.2 |
11.7 |
11.7 |
0.0038 |
0.554 |
50 |
1.4 |
13.9 |
13.9 |
0.0037 |
0.386 |
70 |
1.4 |
16 |
16 |
0.0032 |
0.272 |
95 |
1.6 |
18.2 |
18.2 |
0.0032 |
0.206 |
120 |
1.6 |
20.2 |
20.2 |
0.0029 |
0.161 |
150 |
1.8 |
22.5 |
22.5 |
0.0029 |
0.129 |
185 |
2.0 |
24.9 |
24.9 |
0.0029 |
0.106 |
240 |
2.2 |
28.4 |
28.4 |
0.0028 |
0.0801 |
GS IEC 60227-3, BS 6004
Rated Voltage: |
300/500V |
Conductor: |
plain annealed copper conductor class 1, GS IEC 60228 |
Insulation: |
PVC |
Maximum conductor operating Temperature in normal use: |
70°C |
Nominal cross sectional area of conductor |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 70°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
0.5 |
0.6 |
1.9 |
2.3 |
0.015 |
36.0 |
0.75 |
0.6 |
2.1 |
2.5 |
0.012 |
24.5 |
1 |
0.6 |
2.2 |
2.7 |
0.011 |
18.1 |
GS IEC 60227-3, BS 6004
Rated Voltage: | 300/500V |
Conductor: | plain annealed copper conductor class 1, GS IEC 60228 |
Insulation: | PVC |
Maximum conductor operating Temperature in normal use: |
70°C
|
Nominal cross sectional area of conductor | Thickness of insulation | Mean overall diameter |
Minimum Insulation resistance at 70°C |
Max. d.c. resistance @20°C | |
Lower limit | Upper limit | ||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
0.5 |
0.6 |
2.1 |
2.5 |
0.013 |
39.0 |
0.75 |
0.6 |
2.2 |
2 7 |
0.011 |
26.0 |
1 |
0.6 |
2.4 |
2.8 |
0.010 |
19.5 |
GS IEC 60227-3, BS 6004
Rated Voltage: |
300/500V |
Conductor: |
annealed plain copper conductor class 1, GS IEC 60228 |
Insulation: |
PVC |
Maximum conductor operating Temperature in normal use: |
90°C |
Nominal cross sectional area of conductor |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 90°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
0.5 |
0.6 |
1.9 |
2.3 |
0.015 |
36.0 |
0.75 |
0.6 |
21 |
2.5 |
0.012 |
24.5 |
1 |
0.6 |
2.2 |
2.7 |
0.011 |
18.1 |
1.5 |
0.7 |
2.6 |
3.2 |
0.011 |
12.1 |
2.5 |
0.8 |
3.2 |
3.9 |
0.009 |
7.4 |
Rated Voltage: |
300/500V |
Conductor: |
plain annealed copper conductor class 5, GS IEC 60228 |
Insulation: |
PVC |
Maximum conductor operating Temperature in normal use: |
90°C |
Nominal cross sectional area of conductor |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 90°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
0.5 |
0.6 |
2.1 |
2.5 |
0.013 |
39.0 |
0.75 |
0.6 |
2 2 |
2 7 |
0.012 |
26.0 |
1 |
0.6 |
2.4 |
2.8 |
0.010 |
19.5 |
1.5 |
0.7 |
2.8 |
3.4 |
0.009 |
13.3 |
2.5 |
0.8 |
3.4 |
4.1 |
0.009 |
8.0 |
Contact our sales team
Our sales team is available for support on size, specification and quotations, speak to our sales team for support on your cable requirements.