The flexible cables are for connections to moveable equipment. Sheathed cables are either single or multicore cables. Our sheathed and non-sheathed products are BASEC approved, CE marked and manufactured in accordance with BS EN 50525-2-31, EN 50525-2-11, IEC 60227-3, IEC 60227-4, IEC 60227-5, BS 6004, and other customer specification.
Sheathed Product Data Tables
BS 6004
Conductor: | Class 2 (annealed plain copper / aluminium) |
Insulation: | PVC |
Sheath: | PVC |
Identification of core: | brown, blue / red, black |
Number and Nominal cross-sectional area of conductors | Radial thickness of insulation | Radial thickness of sheath | Approximate overall dimensions |
mm2 |
mm |
mm |
mm |
2x1.5 |
0.6 |
0.90 |
4.7 x 7.4 |
2x1.5 |
0.7 |
0.90 |
5.4 x 8.4 |
2x2.5 |
0.8 |
1.0 |
6.2 x 9.8 |
2x4 |
0.8 |
1.0 |
7.2 x 11.5 |
2x6 |
0.8 |
1.1 |
8.0 x 13.0 |
Rated Voltage: | 300/500V |
Conductor: | annealed plain copper conductor class 1&2, GS IEC 60228 |
Insulation: | PVC |
Sheath: | PVC |
Maximum conductor operating Temperature in normal use: | 70°C |
Number and Nominal cross sectional area of conductors |
Class of conductor IEC 60228 |
Insulation Thickness Specified value |
Thickness of inner covering Approximate value |
Thickness of sheath Specified value |
Mean overall diameter Lower Upper limit limit |
Minimum Insulation resistance at 70°C | |
mm2 |
mm |
mm |
mm |
mm |
mm |
mm |
MΩ/km |
1x1.5 |
1 |
0.7 |
0.8 |
4.2 |
4.8 |
0.011 |
|
1x1.5 |
2 |
0.7 |
0.8 |
4.3 |
4.9 |
0.010 |
|
1x2.5 |
1 |
0.8 |
0.8 |
4.8 |
5.5 |
0.010 |
|
1x2.5 |
2 |
0.8 |
0.8 |
4.9 |
5.6 |
0.009 |
|
1x4 |
1 |
0.8 |
0.9 |
5.4 |
6.2 |
0.085 |
|
1x4 |
2 |
0.8 |
0.9 |
5.6 |
6.4 |
0.0077 |
|
1x6 |
1 |
0.8 |
0.9 |
5.9 |
6.8 |
0.007 |
|
1x6 |
2 |
0.8 |
0.9 |
6.1 |
7 |
0.0065 |
|
1x10 |
2 |
1.0 |
0.9 |
7.4 |
8.5 |
0.0052 |
|
1x16 |
2 |
1 0 |
1 0 |
8.4 |
9.8 |
0.005 |
|
1x25 |
2 |
1.2 |
1.1 |
10.3 |
11.9 |
0.005 |
|
1x35 |
2 |
1.2 |
1.1 |
11.2 |
13.1 |
0.0044 |
|
2x1.5 |
1 |
0.7 |
0.4 |
1.2 |
7.6 |
10 |
0.011 |
2x1.5 |
2 |
0.7 |
0.4 |
1.2 |
7.8 |
10.5 |
0.010 |
2x1.5 |
1 |
0.8 |
0.4 |
1.2 |
8.6 |
11.5 |
0.010 |
2x2.5 |
2 |
0.8 |
0.4 |
1.2 |
9.0 |
12 |
0.009 |
2x4 |
1 |
0.8 |
0.4 |
1.2 |
9.6 |
12.5 |
0.0085 |
2x4 |
2 |
0.8 |
04 |
1.2 |
10.0 |
13 |
0.0077 |
2x6 |
1 |
0.8 |
0.4 |
1.2 |
10.5 |
13.5 |
0.007 |
2x6 |
2 |
0.8 |
0.4 |
1.2 |
11.0 |
14 |
0.0065 |
2x10 |
1 |
1.0 |
0.6 |
1.4 |
13.0 |
16.5 |
0.007 |
2x10 |
2 |
1.0 |
0.6 |
1.4 |
13.5 |
17.5 |
0.0065 |
2x16 |
2 |
1.0 |
0.6 |
1.4 |
15.5 |
20 |
0.0052 |
2x25 |
2 |
1.2 |
0.8 |
1.4 |
18.5 |
24 |
0.005 |
2x35 |
2 |
12 |
1.0 |
1.6 |
21.0 |
27.5 |
0.0044 |
3x1.5 |
1 |
0.7 |
0.4 |
1.2 |
8 |
10.5 |
0.011 |
3x1.5 |
2 |
07 |
0.4 |
1.2 |
8.2 |
11 |
0.010 |
3x2.5 |
1 |
0.8 |
0.4 |
1.2 |
9.2 |
12 |
0.010 |
3x2.5 |
2 |
0.8 |
0.4 |
1.2 |
9.4 |
12.5 |
0.0090 |
3x4 |
1 |
0.8 |
0.4 |
1.2 |
10 |
13 |
0.0085 |
3x4 |
2 |
0.8 |
0.4 |
1.2 |
10.5 |
13.5 |
0.0077 |
3x6 |
1 |
0.8 |
0.4 |
1.4 |
11.5 |
14.5 |
0.0070 |
3x6 |
2 |
0.8 |
0.4 |
1.4 |
12.0 |
15.5 |
0.0065 |
3x10 |
1 |
1.0 |
0.6 |
1.4 |
14.0 |
17.5 |
0.0070 |
3x10 |
2 |
1.0 |
0.6 |
1.4 |
14.5 |
19.0 |
0.0065 |
3x16 |
2 |
1.0 |
0.8 |
1.4 |
16.5 |
21.5 |
0.0052 |
3x25 |
2 |
1.2 |
0.8 |
1.6 |
20.5 |
26.0 |
0.0050 |
3x35 |
2 |
1.2 |
1.0 |
1.6 |
22.0 |
29.0 |
0.0044 |
4x1.5 |
1 |
0.7 |
0.4 |
1.2 |
8.6 |
11.5 |
0.011 |
4x1.5 |
2 |
0.7 |
0.4 |
1.2 |
9 |
12 |
0.010 |
4x2.5 |
1 |
0.8 |
0.4 |
1.2 |
10.0 |
13.0 |
0.010 |
4x2.5 |
2 |
0.8 |
0.4 |
1.2 |
10.0 |
13.5 |
0.0090 |
4x4 |
1 |
0.8 |
0.4 |
1.4 |
11.5 |
14.5 |
0.0085 |
4x4 |
2 |
0.8 |
0.4 |
1.4 |
12.0 |
15.0 |
0.0077 |
4x6 |
1 |
0.8 |
0.6 |
1.4 |
12.5 |
16.0 |
0.0070 |
4x6 |
2 |
0.8 |
0.6 |
1.4 |
13.0 |
17.0 |
0.0065 |
4x10 |
1 |
1.0 |
0.6 |
1.4 |
15.5 |
19.0 |
0.0070 |
4x10 |
2 |
1.0 |
0.6 |
1.4 |
16.0 |
20.5 |
0.0065 |
4x16 |
2 |
1.0 |
0.8 |
1.4 |
18.0 |
23.5 |
0.0052 |
4x25 |
2 |
1.2 |
1.0 |
1.6 |
22.5 |
28.5 |
0.0050 |
4x35 |
2 |
1.2 |
1.0 |
1.6 |
24.5 |
32.0 |
0.0044 |
5x1.5 |
1 |
0.7 |
0.4 |
1.2 |
9.4 |
120 |
0.011 |
5x1.5 |
2 |
0.7 |
0.4 |
1.2 |
9.8 |
12.5 |
0.010 |
5x2.5 |
1 |
0.8 |
0.4 |
1.2 |
11.0 |
14.0 |
0.010 |
5x2.5 |
2 |
0.8 |
0.4 |
1.2 |
11.0 |
14.5 |
0.009 |
5x4 |
1 |
0.8 |
0.6 |
1.4 |
12.5 |
16.0 |
0.0085 |
5x4 |
2 |
0.8 |
0.6 |
1.4 |
13.0 |
17.0 |
0.0077 |
5x6 |
1 |
0.8 |
0.6 |
1.4 |
13.5 |
17.5 |
0.0070 |
5x6 |
2 |
0.8 |
0.6 |
1.4 |
14.5 |
18.5 |
0.0065 |
5x10 |
1 |
1.0 |
0.6 |
1.4 |
17.0 |
21.0 |
0.0070 |
5x10 |
2 |
1.0 |
0.6 |
1.4 |
17.5 |
22.0 |
0.0065 |
5x16 |
2 |
1.0 |
0.8 |
1.6 |
20.5 |
26.0 |
0.0052 |
5x25 |
2 |
1.2 |
1.0 |
1.6 |
24.5 |
31.5 |
0.0050 |
5x35 |
2 |
1.2 |
1.2 |
1.6 |
27.0 |
35.0 |
0.0044 |
GS IEC 60227-5, BS 6500
Rated Voltage: | 300/300V |
Conductor: | annealed plain copper conductor class 5, GS IEC 60228 |
Insulation: | PVC |
Sheath: | PVC |
Maximum conductor operating TemPerature in normal use: | 70°C |
Nominal cross sectional area of conductor | Thickness of insulation | Mean overall diameter | Minimum Insulation resistance at 70°C | Max. d.c. resistance @20°C | |
Lower limit | Upper limit | ||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
2x0.5 |
0.5 |
0.6 |
4.6 or 3x4.9 |
5.9 or 3.7x5.9 |
0.012 |
2x0.75 |
0.5 . |
0.6 |
4.9 or 3.2x5.2 |
6.3 or 3.8x6.3 |
0.010 |
3x0.5 |
0.5 |
0.6 |
4.9 |
6.3 |
0.012 |
3x0.75 |
0.5 |
0.6 |
5.2 |
6.7 |
0.010 |
GS IEC 60227- 5, BS 6500
Rated Voltage: | 300/500V |
Conductor: | annealed plain copper conductor class 5, GS IEC 60228 |
Insulation: | PVC |
Sheath: | PVC |
Maximum conductor operating temperature in normal use: | 70°C |
Number and Nominal cross sectional area of conductors |
Thickness of insulation Specified value |
Thickness of sheath Specified value |
Mean overall dimensions | Minimum insulation resistance at 90° C | |
Lower limit | Upper limit | ||||
mm2 |
mm |
mm |
mm |
mm |
MΩ/km |
2X0.75 |
0.6 |
0.8 |
5.7 or 3.7x6.0 |
7.2 or 4.5x7.2 |
0.011 |
2X1 |
0.6 |
0.8 |
5.9 or 3.9x6.2 |
7.5 or 4.7x7.5 |
0.010 |
2X1.5 |
0.7 |
0 8 |
6.8 |
8.6 |
0.010 |
2X2.5 |
0.8 |
1 0 |
8 4 |
10.6 |
0.009 |
3 X 0.75 |
0.6 |
0 8 |
6.0 |
7.6 |
0.011 |
3X1 |
0.6 |
0.8 |
6.3 |
8.0 |
0.010 |
3X1.5 |
0.7 |
0.9 |
7.4 |
9.4 |
0.010 |
3X2.5 |
0.8 |
1.1 |
9.2 |
11.4 |
0.009 |
4 X 0.75 |
0.6 |
0.8 |
6.6 |
8.3 |
0.011 |
4X1 |
0.6 |
0.9 |
7.1 |
9.0 |
0.010 |
4X1.5 |
0.7 |
1 |
8.4 |
10.5 |
0.010 |
4X2.5 |
0.8 |
1.1 |
10.1 |
12.5 |
0.009 |
5 X 0.75 |
0.6 |
0.9 |
7.4 |
9.3 |
0.011 |
5X1 |
0.6 |
0.9 |
7.8 |
9.8 |
0.010 |
5 X 1.5 |
0.7 |
1.1 |
9.3 |
11.6 |
0.010 |
5X2.5 |
0.8 |
1.2 |
11.2 |
13.9 |
0.009 |
GS IEC 60227-5, BS 6500
Rated Voltage: | 300/300V |
Conductor: | annealed plain copper conductor class 5, GS IEC 60228 |
Insulation: | PVC |
Sheath: | PVC |
Maximum conductor operating Temperature in normal use: | 90°C |
Nominal cross sectional area of conductor |
Thickness of insulation Specified value |
Thickness of sheath Specified value |
Mean overall diameter |
Minimum insulation resistance at 90°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
mm |
MΩ/km |
2x0.5 |
0.5 |
0.6 |
4.6 or 3x4.9 |
5.9 or 3.7x5.9 |
0.012 |
2x0.75 |
0.5 |
0.6 |
4.6 or 3.2x5.2 |
6.3 or 3.8x6.3 |
0.010 |
3x0.5 |
0.5 |
0.6 |
4.9 |
6.3 |
0.012 |
3x0.75 |
0.5 |
0.6 |
5.2 |
6.7 |
0.010 |
3x1 |
0.6 |
0.8 |
63 |
8.0 |
0.010 |
3x0.15 |
0.7 |
0.9 |
7.4 |
9.4 |
0.010 |
3x0.25 |
0.8 |
1.1 |
9.2 |
11.4 |
0.009 |
4x0.75 |
0.6 |
0.8 |
6.6 |
8.3 |
0.011 |
4x1 |
0.6 |
0.9 |
7.1 |
9.0 |
0.010 |
4x1.5 |
0.7 |
1.0 |
8.4 |
10.5 |
0.010 |
4x2.5 |
0.8 |
1.1 |
10.1 |
12.5 |
0.009 |
4x0.75 |
0.6 |
0.9 |
7.4 |
9.3 |
0.011 |
5x1 |
0.6 |
0.9 |
7.8 |
9.8 |
0.010 |
5x1.5 |
0.7 |
1.1 |
9.3 |
11.6 |
0.010 |
5x2.5 |
0.8 |
1.2 |
11.2 |
13.9 |
0.009 |
GS IEC 60227-5, BS 6500
Rated Voltage: | 300/500V |
Conductor: | annealed plain copper conductor class 5, GS IEC 60228 |
Insulation: | PVC |
Sheath: | PVC |
Maximum conductor operating Temperature in normal use: |
90°C |
Nominal cross sectional area of conductor |
Thickness of insulation Specified value |
Thickness of sheath Specified value |
Mean overall diameter | Minimum insulation resistance at 90°C | |
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
mm |
MΩ/km |
2x0.75 |
0.6 |
0.8 |
5.7 or 3.7x6.0 |
7.2 or 4.5x 7.2 |
0.011 |
2x1 |
0.6 |
0.8 |
5.9 or 3.9x6.2 |
7.5 or 4.7x 7.5 |
0.010 |
2x1.5 |
0.7 |
0.8 |
6.8 |
8.6 |
0.010 |
2x2.5 . |
0.8 |
1.0 |
8.4 |
10.6 |
0.009 |
3x0.75 |
0.6 |
0.8 |
6.0 |
7.6 |
0.011 |
3x1 |
0.6 |
0.8 |
6.3 |
8.0 |
0.010 |
3x1.5 |
0.7 |
0.9 |
7.4 |
9.4 |
0.010 |
3x2.5 |
0.8 |
1.1 |
9.2 |
11.4 |
0.009 |
4x0.75 |
0.6 |
0.8 |
6.6 |
8.3 |
0.011 |
4x1 |
0.6 |
0.9 |
7 1 |
9.0 |
0.010 |
4x1.5 |
0.7 |
1.0 |
8.4 |
10.5 |
0.010 |
4x2.5 |
0.8 |
1.1 |
10.1 |
12.5 |
0.009 |
5x0.75 |
0.6 |
0.9 |
7.4 |
9.3 |
0.011 |
5x1 |
0.6 |
0.9 |
7.8 |
9.8 |
0.010 |
5x1.5 |
0.7 |
1.1 |
9.3 |
11.6 |
0.010 |
5x2.5 |
0.8 |
1.2 |
11.2 |
13.9 |
0.009 |
Non-Sheathed Product Data Tables
GS IEC 60227-3, BS 6004
Rated Volage: | 450/750V |
Conductor: | Plain annealed copper conductor class 1&2, GS IEC 60228 |
Insulation: | PVC |
Maximum conductor operating temperature in normal use: | 70°C |
Nominal cross sectional area of conductor |
Class of conductor IEC 60228 |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 70°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
|||||
mm2 |
mm |
mm |
mm |
mm |
MΩ/km |
Ω/km |
1.5 |
1 |
0.7 |
2.6 |
3.2 |
0.011 |
12.10 |
1.5 |
2 |
0.7 |
2.7 |
3.3 |
0.010 |
12.10 |
2.5 |
1 |
0.8 |
3.2 |
3.9 |
0.010 |
7.41 |
2.5 |
2 |
0.8 |
3.3 |
4 |
0.009 |
7.41 |
4 |
1 |
0.8 |
3.6 |
4.4 |
0.0085 |
4.61 |
4 |
2 |
0.8 |
3.8 |
4.6 |
0.0077 |
4.61 |
6 |
1 |
0.8 |
4.1 |
5 |
0.007 |
3.08 |
6 |
2 |
0.8 |
4.3 |
5.2 |
0.0065 |
3.08 |
10 |
1 |
1.0 |
5.3 |
6.4 |
0.007 |
1.83 |
10 |
2 |
1.0 |
5.6 |
6.7 |
0.0065 |
1.83 |
16 |
2 |
1.0 |
6.4 |
7.8 |
0.005 |
1.15 |
25 |
2 |
12 |
8.1 |
9.7 |
0.005 |
0.727 |
35 |
2 |
1.2 |
9.0 |
10.9 |
0.0043 |
0.524 |
50 |
2 |
1.4 |
10.6 |
12.8 |
0.0043 |
0.387 |
70 |
2 |
14 |
12.1 |
14.6 |
0.0035 |
0.268 |
95 |
2 |
1.6 |
14.1 |
17.1 |
0.0035 |
0.193 |
120 |
2 |
1.6 |
15.6 |
|18.8 |
0.0032 |
0.153 |
150 |
2 |
1.8 |
17.3 |
20.9 |
0.0032 |
0.124 |
185 |
2 |
2.0 |
19.3 |
23.3 |
0.0032 |
0.101 |
240 |
2 |
2.2 |
22.0 |
26.6 |
0.0032 |
0.0775 |
300 |
2 |
2.4 |
24.5 |
29.6 |
0.003 |
0.0620 |
400 |
2 |
2.6 |
27.5 |
33.2 |
0.0028 |
0.0465 |
GS IEC 60227-3, BS 6004
Rated Voltage: | 450/750V |
Conductor: | annealed plain copper conductor class 5, GS IEC 60228 |
Insulation: | PVC |
Maximum conductor operating Temperature in normal use: | 70°C |
Nominal cross sectional area of conductor |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 70°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
1.5 |
0.7 |
2.8 |
3.4 |
0.010 |
13.3 |
2.5 |
0.8 |
4.1 |
4.1 |
0.009 |
7.98 |
4 |
0.8 |
4.8 |
4.8 |
0.007 |
4.95 |
6 |
0.8 |
5.3 |
5.3 |
0.006 |
3 3 |
10 |
1.0 |
6.8 |
6.8 |
0.0056 |
1.91 |
16 |
1.0 |
8.1 |
8.1 |
0.0046 |
1.21 |
25 |
1.2 |
10.2 |
10.2 |
0.0044 |
0.78 |
35 |
1.2 |
11.7 |
11.7 |
0.0038 |
0.554 |
50 |
1.4 |
13.9 |
13.9 |
0.0037 |
0.386 |
70 |
1.4 |
16 |
16 |
0.0032 |
0.272 |
95 |
1.6 |
18.2 |
18.2 |
0.0032 |
0.206 |
120 |
1.6 |
20.2 |
20.2 |
0.0029 |
0.161 |
150 |
1.8 |
22.5 |
22.5 |
0.0029 |
0.129 |
185 |
2.0 |
24.9 |
24.9 |
0.0029 |
0.106 |
240 |
2.2 |
28.4 |
28.4 |
0.0028 |
0.0801 |
GS IEC 60227-3, BS 6004
Rated Voltage: |
300/500V |
Conductor: |
plain annealed copper conductor class 1, GS IEC 60228 |
Insulation: |
PVC |
Maximum conductor operating Temperature in normal use: |
70°C |
Nominal cross sectional area of conductor |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 70°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
0.5 |
0.6 |
1.9 |
2.3 |
0.015 |
36.0 |
0.75 |
0.6 |
2.1 |
2.5 |
0.012 |
24.5 |
1 |
0.6 |
2.2 |
2.7 |
0.011 |
18.1 |
GS IEC 60227-3, BS 6004
Rated Voltage: | 300/500V |
Conductor: | plain annealed copper conductor class 1, GS IEC 60228 |
Insulation: | PVC |
Maximum conductor operating Temperature in normal use: |
70°C
|
Nominal cross sectional area of conductor | Thickness of insulation | Mean overall diameter |
Minimum Insulation resistance at 70°C |
Max. d.c. resistance @20°C | |
Lower limit | Upper limit | ||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
0.5 |
0.6 |
2.1 |
2.5 |
0.013 |
39.0 |
0.75 |
0.6 |
2.2 |
2 7 |
0.011 |
26.0 |
1 |
0.6 |
2.4 |
2.8 |
0.010 |
19.5 |
GS IEC 60227-3, BS 6004
Rated Voltage: |
300/500V |
Conductor: |
annealed plain copper conductor class 1, GS IEC 60228 |
Insulation: |
PVC |
Maximum conductor operating Temperature in normal use: |
90°C |
Nominal cross sectional area of conductor |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 90°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
0.5 |
0.6 |
1.9 |
2.3 |
0.015 |
36.0 |
0.75 |
0.6 |
21 |
2.5 |
0.012 |
24.5 |
1 |
0.6 |
2.2 |
2.7 |
0.011 |
18.1 |
1.5 |
0.7 |
2.6 |
3.2 |
0.011 |
12.1 |
2.5 |
0.8 |
3.2 |
3.9 |
0.009 |
7.4 |
Rated Voltage: |
300/500V |
Conductor: |
plain annealed copper conductor class 5, GS IEC 60228 |
Insulation: |
PVC |
Maximum conductor operating Temperature in normal use: |
90°C |
Nominal cross sectional area of conductor |
Thickness of insulation |
Mean overall diameter |
Minimum Insulation resistance at 90°C |
Max. d.c. resistance @20°C |
|
Lower limit |
Upper limit |
||||
mm2 |
mm |
mm |
mm |
MΩ/km |
Ω/km |
0.5 |
0.6 |
2.1 |
2.5 |
0.013 |
39.0 |
0.75 |
0.6 |
2 2 |
2 7 |
0.012 |
26.0 |
1 |
0.6 |
2.4 |
2.8 |
0.010 |
19.5 |
1.5 |
0.7 |
2.8 |
3.4 |
0.009 |
13.3 |
2.5 |
0.8 |
3.4 |
4.1 |
0.009 |
8.0 |