Power Cables are an assembly of one or more cores having a common sheath for transmitting power. They are for fixed power supply to buildings and electrical equipment. Power cables can be buried directly in ground, installed in trays or in air depending on construction and where it is installed. They are also available with both aluminium and copper conductor based on application or customer preference.
We are fully equipped to produce excellent Low Voltage Power Cables in accordance to all international and local standards.
Product Data Tables
Conductor: | class 2 (annealed plain copper / Aluminium) |
Insulation: | XLPE |
Cuter sheath: | PVC |
Identification of cores | Red |
Single Core Cables With Circular Stranded Copper / Aluminium Conductor
Nominal cross sectional area of conductor a | Thickness of insulation | Thickness of outer sheath | Approximate overall diameter |
mm2 | mm | mm | mm |
50 | 1.0 | 1.4 | 16.7 |
70 | 1.1 | 1.4 | 18.7 |
95 | 1.1 | 1.5 | 21.8 |
120 | 1.2 | 1.5 | 22.4 |
150 | 1.4 | 1.6 | 24.8 |
185 | 1.6 | 1.6 | 27.0 |
240 | 1.7 | 1.7 | 30.1 |
300 | 1.8 | 1.8 | 32.9 |
400 | 2.0 | 1.9 | 36.5 |
500 | 2.2 | 2.0 | 40.2 |
630 | 2.4 | 2.2 | 45.0 |
800 | 2.6 | 2.3 | 49.9 |
1000 | 2.8 | 2.4 | 55.0 |
a circular stranded conductor (class 2)
Conductor: | Class 2 ( annealed plain copper/aluminium ) |
Insulation: | XLPE |
Outer sheath: | PVC |
Identification of cores: | Red/Black/Customer requirement |
Nominal cross sectional area of conductor | Thickness of insulation | Thickness of outer sheath | Approximate overall diameter |
mm2 | mm | mm | mm |
25 | 0.9 | 1.4 | 14.0 |
35 | 0.9 | 1.4 | 15.2 |
50 | 1.0 | 1.4 | 16.7 |
70 | 1.1 | 1.5 | 18.9 |
95 | 1.1 | 1.5 | 20.8 |
120 | 1.2 | 1.6 | 22.8 |
150 | 1.4 | 1.6 | 24.8 |
185 | 1.6 | 1.8 | 31.4 |
240 | 1.7 | 1.8 | 30.3 |
300 | 1.8 | 1.9 | 33.1 |
400 | 2.0 | 2.0 | 36.7 |
500 | 2.2 | 2.2 | 40.6 |
630 | 2.4 | 2.3 | 45.2 |
IEC 60502-1
Conductor: | class 2 (annealed plain copper/aluminium) |
Insulation | XLPE |
Inner and outer sheath: | PVC |
Identification of core: | black/red |
Armouring: | Aluminium wire armour |
SINGLE-CORE CABLES WITH CIRCULAR STRANDED COPPER/ALUMINIUM CONDUCTOR
Nominal cross sectional area of conductor a | Thickness of insulation | Thickness of inner sheath | Nominal steel armour wire diameter | Thickness of outer sheath | Approximate overall diameter |
mm2 |
mm |
mm |
mm |
mm |
mm |
50 |
1.0 |
1.0 |
1.7 |
1.8 |
24.9 |
70 |
1.1 |
1.0 |
1.7 |
1.8 |
26.9 |
95 |
1.1 |
1.0 |
1.7 |
1.8 |
28.8 |
120 |
1.2 |
1.0 |
1.7 |
1.8 |
30.6 |
150 |
1.4 |
1.0 |
1.7 |
1.8 |
32.6 |
185 |
1.6 |
1.0 |
2.0 |
1.9 |
35.0 |
240 |
1.7 |
1.0 |
2.0 |
2.0 |
38.6 |
300 |
1.8 |
1.2 |
2.0 |
2.1 |
41.9 |
400 |
2.0 |
1.2 |
2.5 |
2.3 |
46.7 |
500 |
2.2 |
1.2 |
2.5 |
2.4 |
50.4 |
630 |
2.4 |
1.4 |
2.5 |
2.6 |
55.6 |
a circular stranded conductor (class 2).
IEC 60502-1
Conductor: |
class 2 (annealed plain copper/aluminium) |
Insulation: Inner and outer sheath: |
XLPE PVC |
Identification of core: |
brown, blue/red, black |
Armouring: |
Aluminium Wire Armour (AWA) Steel Wire Armour subject to availability |
TWO-CORE CABLES WITH STRANDED COPPER CONDUCTOR
Nominal cross sectional area of conductor |
Thickness of insulation |
Thickness of inner sheath |
Nominal AWA diameter |
Thickness of outer sheath |
Approximate overall diameter |
mm2 |
mm |
mm |
mm |
mm |
mm |
4 |
0.7 |
1.0 |
2.0 |
1.8 |
22.5 |
6 |
0.7 |
1.0 |
2.0 |
1.8 |
23.6 |
10 |
0.7 |
1.0 |
2.0 |
1.8 |
25.5 |
16 |
0.7 |
1.0 |
2.0 |
1.8 |
27.6 |
25 |
0.9 |
1.0 |
2.0 |
1.8 |
31.0 |
35 |
0.9 |
1.0 |
2.0 |
1.9 |
33.5 |
50 |
1.0 |
1.0 |
2.0 |
2.0 |
36.8 |
70 |
1.1 |
1.2 |
2.0 |
2.1 |
41.4 |
95 |
1.1 |
1.2 |
2.0 |
2.3 |
45.6 |
Up to 240mm2
IEC 60502-1
Conductor: |
class 2 (annealed plain copper/aluminium) |
Insulation: |
XLPE |
Inner and outer sheath: |
PVC |
Identification of cores: |
brown, black, grey/ red, yellow, blue |
Armouring: |
Aluminium Wire Armour (AWA) Steel Wire Armour subject to availability |
THREE-CORE CABLES WITH STRANDED COPPER/ALUMINIUM CONDUCTOR
Nominal cross sectional area of conductor |
Thickness of insulation |
Thickness of inner sheath |
Nominal AWA diameter |
Thickness of outer sheath |
Approximate overall diameter |
mm2 |
mm |
mm |
mm |
mm |
mm |
4a |
0.7 |
1.0 |
2.0 |
1.8 |
23.1 |
6a |
0.7 |
1.0 |
2.0 |
1.8 |
24.4 |
10a |
0.7 |
1.0 |
2.0 |
1.8 |
26.4 |
16a |
0.7 |
1.0 |
2.0 |
1.8 |
28.6 |
25b |
0.9 |
1 0 |
2.0 |
1.8 |
28.7 |
35b |
0.9 |
1.0 |
2.0 |
1.8 |
30.7 |
50b |
1.0 |
1.0 |
2.0 |
1.8 |
32.4 |
70b |
1.1 |
1.0 |
2.0 |
2.0 |
36.9 |
95b |
1.1 |
1.0 |
2.0 |
2.1 |
40.0 |
120b |
1.2 |
1.2 |
2.0 |
2.2 |
43.5 |
150 |
1.4 |
1.2 |
2.5 |
2.3 |
47.8 |
185 |
1.6 |
1.4 |
2.5 |
2.5 |
52.4 |
240 |
1.7 |
1.4 |
2.5 |
2.6 |
57.0 |
IEC 60502-1
Conductor: | class 2 (annealed plain copper/alumlnlum) |
Insulation: | XLPE |
Inner & outer sheath: | PVC |
Identification of core: | blue, brown, black, grey / yellow, blue, black, red |
Armouring: |
Aluminium Wire Armour (AWA) Steel Wire Armour subject to availability |
FOUR – CORE CABLES WITH STRANDED COPPER / ALUMINIUM CONDUCTOR
Nominal cross sectional area of conductor | Thickness of insulation | Thickness of inner sheath | Nominal AWA diameter | Thickness of outer sheath | Approximate overall diameter |
mm2 |
mm |
mm |
mm |
mm |
mm |
4a |
0.7 |
1.0 |
2.0 |
1.8 |
24.2 |
6a |
0.7 |
1.0 |
2.0 |
1.8 |
25.2 |
10a |
0.7 |
1.0 |
2.0 |
1.8 |
27.8 |
16a |
0.7 |
1.0 |
2.0 |
1.8 |
30.3 |
25b |
0.9 |
1.0 |
2.0 |
1.8 |
31.8 |
35b |
0.9 |
1.0 |
2.0 |
1.9 |
34.0 |
50b |
1.0 |
1.0 |
2.0 |
2.0 |
36.9 |
70b |
1.1 |
1.2 |
2.0 |
2.1 |
41.7 |
95b |
1.1 |
1 2 |
2.0 |
2.3 |
45.6 |
120b |
1.2 |
1.2 |
2.5 |
2.4 |
50.3 |
150b |
1.4 |
1.4 |
2.5 |
2.6 |
54.8 |
185 b |
1.6 |
1.4 |
2.5 |
2.7 |
59.5 |
240b |
1.7 |
1.6 |
3.0 |
3.0 |
66.9 |
a circular stranded conductor (class 2)
b sector shaped stranded conductor (class 2)
IEC 60502-1
Conductor: | class 2 (annealed plain copper/alumlnlum) |
Insulation: | XLPE |
Inner & outer sheath: | PVC |
Identification of core: | blue, brown, black, grey / yellow, blue, black, red |
Armouring: |
Aluminium Wire Armour (AWA) Steel Wire Armour subject to availability |
FOUR – CORE CABLES WITH STRANDED COPPER / ALUMINIUM CONDUCTOR
Nominal cross sectional area of conductor | Thickness of insulation | Thickness of inner sheath | Nominal AWA diameter | Thickness of outer sheath | Approximate overall diameter |
mm2 |
mm |
mm |
mm |
mm |
mm |
4a |
0.7 |
1.0 |
2.0 |
1.8 |
24.2 |
6a |
0.7 |
1.0 |
2.0 |
1.8 |
25.2 |
10a |
0.7 |
1.0 |
2.0 |
1.8 |
27.8 |
16a |
0.7 |
1.0 |
2.0 |
1.8 |
30.3 |
25b |
0.9 |
1.0 |
2.0 |
1.8 |
31.8 |
35b |
0.9 |
1.0 |
2.0 |
1.9 |
34.0 |
50b |
1.0 |
1.0 |
2.0 |
2.0 |
36.9 |
70b |
1.1 |
1.2 |
2.0 |
2.1 |
41.7 |
95b |
1.1 |
1 2 |
2.0 |
2.3 |
45.6 |
120b |
1.2 |
1.2 |
2.5 |
2.4 |
50.3 |
150b |
1.4 |
1.4 |
2.5 |
2.6 |
54.8 |
185 b |
1.6 |
1.4 |
2.5 |
2.7 |
59.5 |
240b |
1.7 |
1.6 |
3.0 |
3.0 |
66.9 |
a circular stranded conductor (class 2)
b sector shaped stranded conductor (class 2)
Contact our sales team
Our sales team is available for support on size, specification and quotations, speak to our sales team for support on your cable requirements.