TCCL EARTH-CABLE

Sheathed and Non-Sheathed cables rated, 300/500V and 450/750V are insulated and/or sheathed cables for a variety of application from fixed wiring for power supply to sockets, switches, and lighting fittings of domestic and commercial buildings to flexible installation.

In fixed wiring applications, the cables are installed in conduit in walls or on surfaces. Non-sheathed cables are utilized in the internal wiring of distribution boards and switchboards.

The flexible cables are for connections to moveable equipment. Sheathed cables are either single or multicore cables. Our sheathed and non-sheathed products are BASEC approved, CE marked and manufactured in accordance with BS EN 50525-2-31, EN 50525-2-11, IEC 60227-3, IEC 60227-4, IEC 60227-5, BS 6004, and other customer specification.

Product Data Tables

GS IEC 60227-3, BS 6004

Rated Volage: 450/750V
Conductor: Plain annealed copper conductor class 1&2, GS IEC 60228
Insulation: PVC
Maximum conductor operating temperature in normal use: 70°C

 

Nominal cross sectional area of conductor

Class of conductor IEC 60228

Thickness of insulation

Mean overall diameter

Minimum Insulation resistance at 70°C

Max. d.c. resistance @20°C

Lower limit

Upper limit

mm2

mm

mm

mm

mm

MΩ/km

Ω/km

1.5

1

0.7

2.6

3.2

0.011

12.10

1.5

2

0.7

2.7

3.3

0.010

12.10

2.5

1

0.8

3.2

3.9

0.010

7.41

2.5

2

0.8

3.3

4

0.009

7.41

4

1

0.8

3.6

4.4

0.0085

4.61

4

2

0.8

3.8

4.6

0.0077

4.61

6

1

0.8

4.1

5

0.007

3.08

6

2

0.8

4.3

5.2

0.0065

3.08

10

1

1.0

5.3

6.4

0.007

1.83

10

2

1.0

5.6

6.7

0.0065

1.83

16

2

1.0

6.4

7.8

0.005

1.15

25

2

12

8.1

9.7

0.005

0.727

35

2

1.2

9.0

10.9

0.0043

0.524

50

2

1.4

10.6

12.8

0.0043

0.387

70

2

14

12.1

14.6

0.0035

0.268

95

2

1.6

14.1

17.1

0.0035

0.193

120

2

1.6

15.6

|18.8

0.0032

0.153

150

2

1.8

17.3

20.9

0.0032

0.124

185

2

2.0

19.3

23.3

0.0032

0.101

240

2

2.2

22.0

26.6

0.0032

0.0775

300

2

2.4

24.5

29.6

0.003

0.0620

400

2

2.6

27.5

33.2

0.0028

0.0465

 

 

GS IEC 60227-3, BS 6004

Rated Voltage: 450/750V
Conductor: annealed plain copper conductor class 5, GS IEC 60228
Insulation: PVC
Maximum conductor operating Temperature in normal use: 70°C

 

Nominal cross sectional area of conductor

Thickness of insulation

Mean overall diameter

Minimum

Insulation resistance at 70°C

Max. d.c. resistance @20°C

Lower limit

Upper limit

mm2

mm

mm

mm

MΩ/km

Ω/km

1.5

0.7

2.8

3.4

0.010

13.3

2.5

0.8

4.1

4.1

0.009

7.98

4

0.8

4.8

4.8

0.007

4.95

6

0.8

5.3

5.3

0.006

3 3

10

1.0

6.8

6.8

0.0056

1.91

16

1.0

8.1

8.1

0.0046

1.21

25

1.2

10.2

10.2

0.0044

0.78

35

1.2

11.7

11.7

0.0038

0.554

50

1.4

13.9

13.9

0.0037

0.386

70

1.4

16

16

0.0032

0.272

95

1.6

18.2

18.2

0.0032

0.206

120

1.6

20.2

20.2

0.0029

0.161

150

1.8

22.5

22.5

0.0029

0.129

185

2.0

24.9

24.9

0.0029

0.106

240

2.2

28.4

28.4

0.0028

0.0801

 

 

GS IEC 60227-3, BS 6004

Rated Voltage:

300/500V

Conductor:

plain annealed copper conductor class 1, GS IEC 60228

Insulation:

PVC

Maximum conductor operating Temperature in normal use:

70°C

 

Nominal cross sectional area of conductor

Thickness of insulation

Mean overall diameter

Minimum

Insulation resistance at 70°C

Max. d.c. resistance @20°C

Lower limit

Upper limit

mm2

mm

mm

mm

MΩ/km

Ω/km

0.5

0.6

1.9

2.3

0.015

36.0

0.75

0.6

2.1

2.5

0.012

24.5

1

0.6

2.2

2.7

0.011

18.1

 

 

GS IEC 60227-3, BS 6004

Rated Voltage: 300/500V
Conductor: plain annealed copper conductor class 1, GS IEC 60228
Insulation: PVC
Maximum conductor operating Temperature in normal use:

70°C

 

 

Nominal cross sectional area of conductor Thickness of insulation Mean overall diameter

Minimum

Insulation resistance at 70°C

Max. d.c. resistance @20°C
Lower limit Upper limit

mm2

mm

mm

mm

MΩ/km

Ω/km

0.5

0.6

2.1

2.5

0.013

39.0

0.75

0.6

2.2

2 7

0.011

26.0

1

0.6

2.4

2.8

0.010

19.5

 

 

 

GS IEC 60227-3, BS 6004

Rated Voltage:

300/500V

Conductor:

annealed plain copper conductor class 1, GS IEC 60228

Insulation:

PVC

Maximum conductor operating Temperature in normal use:

90°C

 

Nominal cross sectional area of conductor

Thickness of insulation

Mean overall diameter

Minimum

Insulation resistance at 90°C

Max. d.c. resistance @20°C

Lower limit

Upper limit

mm2

mm

mm

mm

MΩ/km

Ω/km

0.5

0.6

1.9

2.3

0.015

36.0

0.75

0.6

21

2.5

0.012

24.5

1

0.6

2.2

2.7

0.011

18.1

1.5

0.7

2.6

3.2

0.011

12.1

2.5

0.8

3.2

3.9

0.009

7.4

 

 

Rated Voltage:

300/500V

Conductor:

plain annealed copper conductor class 5, GS IEC 60228

Insulation:

PVC

Maximum conductor operating Temperature in normal use:

90°C

 

Nominal cross sectional area of conductor

Thickness of insulation

Mean overall diameter

Minimum

Insulation resistance at 90°C

Max. d.c. resistance @20°C

Lower limit

Upper limit

mm2

mm

mm

mm

MΩ/km

Ω/km

0.5

0.6

2.1

2.5

0.013

39.0

0.75

0.6

2 2

2 7

0.012

26.0

1

0.6

2.4

2.8

0.010

19.5

1.5

0.7

2.8

3.4

0.009

13.3

2.5

0.8

3.4

4.1

0.009

8.0

 

 

Contact our sales team

Our sales team is available for support on size, specification and quotations, speak to our sales team for support on your cable requirements.

focus-quality

Focus on Quality

Our Quality Management System for inspection, monitoring and testing ensures conformity of product to specified requirements from Receipt of Raw Material to Despatch to Customer

quality-lab

Quality Lab

To ensure continuous delivery of quality cables, we have setup a world-class cable testing laboratory, staffed with technical experts who ensure the quality of our cables

Scroll to Top